Modeling of PV Module and DC/DC Converter Assembly for the Analysis of Induced Transient Response Due to Nearby Lightning Strike

Photovoltaic (PV) systems are subject to nearby lightning strikes that can contribute to extremely high induced overvoltage transients. Recently, the authors introduced a 3D semianalytical method to study the electromagnetic transients caused by these strikes in a PV module. In the present paper we...

Descripción completa

Detalles Bibliográficos
Autores: Formisano, Alessandro, de-la-Casa-Hernández, Jesús, Petrarca, Carlo, Sánchez-Sutil, Francisco
Tipo de recurso: artículo
Estado:Versión publicada
Fecha de publicación:2021
País:España
Institución:Universidad de Jaén
Repositorio:RUJA. Repositorio Institucional de la Producción Científica de la Universidad de Jaén
OAI Identifier:oai:ruja.ujaen.es:10953/6119
Acceso en línea:https://doi.org/10.3390/electronics10020120
https://hdl.handle.net/10953/6119
Access Level:acceso abierto
Palabra clave:Photovoltaic
Lightning protection
Lumped-equivalent circuit
Electromagnetic fields
Lightning-induced voltage
Indirect lightning
Transient overvoltage
Computer simulation
Dynamic impedance model
AC and DC parameters
621.35
Descripción
Sumario:Photovoltaic (PV) systems are subject to nearby lightning strikes that can contribute to extremely high induced overvoltage transients. Recently, the authors introduced a 3D semianalytical method to study the electromagnetic transients caused by these strikes in a PV module. In the present paper we develop an improved model of the PV module that: (a) takes into account high-frequency effects by modelling capacitive and inductive couplings; (b) considers the electrical insulation characteristics of the module; (c) includes the connection to a DC/DC converter. The whole process involves three major steps, i.e., the magnetic-field computation, the evaluation of both common-mode- and differential-mode-induced voltages across the PV module, and the use of the calculated voltages as input to a lumped equivalent circuit of the PV module connected to the DC/DC converter. In such a framework, the influence of the PV operating condition on the resulting electrical stresses is assessed; moreover, the relevance or insignificance of some parameters, such as the module insulation or the frame material, is demonstrated. Finally, results show that the induced overvoltage are highly dependent both on the grounding of the conducting parts and on the external conditions such as lightning current waveforms and lightning channel (LC) geometry.