Improvements in the cooling capacity and the COP of a transcritical CO 2 refrigeration plant operating with a thermoelectric subcooling system

Restrictive environmental regulations are driving the use of CO 2 as working fluid in commercial vapour compression plants due to its ultra-low global warming potential (GWP 100 = 1) and its natural condition. However, at high ambient temperatures transcritical operating conditions are commonly achi...

Descripción completa

Detalles Bibliográficos
Autores: Astrain Ulibarrena, David, Merino Vicente, Amaya, Catalán Ros, Leyre, Aranguren Garacochea, Patricia, Araiz Vega, Miguel, Sánchez, Daniel, Cabello, Ramón, Llopis, R.
Tipo de recurso: artículo
Estado:Versión aceptada para publicación
Fecha de publicación:2019
País:España
Institución:Universidad Pública de Navarra
Repositorio:Academica-e. Repositorio Institucional de la Universidad Pública de Navarra
OAI Identifier:oai:academica-e.unavarra.es:2454/36154
Acceso en línea:https://hdl.handle.net/2454/36154
Access Level:acceso abierto
Palabra clave:CO2
Subcooling
R744
Thermoelectricity
Transcritical
COP
Computational model
Descripción
Sumario:Restrictive environmental regulations are driving the use of CO 2 as working fluid in commercial vapour compression plants due to its ultra-low global warming potential (GWP 100 = 1) and its natural condition. However, at high ambient temperatures transcritical operating conditions are commonly achieved causing low energy efficiencies in refrigeration facilities. To solve this issue, several improvements have been implemented, especially in large centralized plants where ejectors, parallel compressors or subcooler systems, among others, are frequently used. Despite their good results, these measures are not suitable for small-capacity systems due mainly to the cost and the complexity of the system. Accordingly, this work presents a new subcooling system equipped with thermoelectric modules (TESC), which thanks to its simplicity, low cost and easy control, results very suitable for medium and small capacity plants. The developed methodology finds the gas-cooler pressure and the electric voltage supplied to the TESC system that maximizes the overall COP of the plant taking into account the ambient temperature, the number of thermoelectric modules used and the thermal resistance of the heat exchangers included in the TESC. The obtained results reveal that, with 20 thermoelectric modules, an improvement of 20% in terms of COP and of 25.6% regarding the cooling capacity can be obtained compared to the base cycle of CO 2 of a small cooling plant refrigerated by air. Compared to a cycle that uses an internal heat exchanger IHX, the improvements reach 12.2% and 19.5% respectively.