Sensitivity Study of the Dynamics of Three-Phase Photovoltaic Inverters With an LCL Grid Filter
[EN] An accurate small-signal model of three-phase photovoltaic (PV) inverters with a high-order grid filter is derived in this paper. The proposed model takes into account the influence of both the inverter operating point and the PV panel characteristics on the inverter dynamic response. A sensiti...
| Autores: | , , , , |
|---|---|
| Tipo de recurso: | artículo |
| Fecha de publicación: | 2009 |
| País: | España |
| Institución: | Universitat Politècnica de València (UPV) |
| Repositorio: | RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia |
| Idioma: | inglés |
| OAI Identifier: | oai:riunet.upv.es:10251/99484 |
| Acceso en línea: | https://riunet.upv.es/handle/10251/99484 |
| Access Level: | acceso abierto |
| Palabra clave: | Distributed generation Modeling and control of power inverters Renewable energies TECNOLOGIA ELECTRONICA |
| Sumario: | [EN] An accurate small-signal model of three-phase photovoltaic (PV) inverters with a high-order grid filter is derived in this paper. The proposed model takes into account the influence of both the inverter operating point and the PV panel characteristics on the inverter dynamic response. A sensitivity study of the control loops to variations of the dc voltage, PV panel transconductance, supplied power, and grid inductance is performed using the proposed small-signal model. Analytical and experimental results carried out on a 100-kW PV inverter are presented. |
|---|