Compensated Load Flow Solutions for Distribution System State Estimation
State estimation of distribution systems typically relies on measurement sets with very low redundancy levels. In this paper, this fact is exploited by first solving a conventional load flow, using exclusively a critical set of measurements, and then compensating the solution to account for the few...
| Autores: | , , , |
|---|---|
| Tipo de recurso: | artículo |
| Estado: | Versión publicada |
| Fecha de publicación: | 2020 |
| País: | España |
| Institución: | Universidad de Sevilla (US) |
| Repositorio: | idUS. Depósito de Investigación de la Universidad de Sevilla |
| OAI Identifier: | oai:idus.us.es:11441/127011 |
| Acceso en línea: | https://hdl.handle.net/11441/127011 https://doi.org/10.3390/en13123100 |
| Access Level: | acceso abierto |
| Palabra clave: | State estimation Distribution systems Load flow |
| Sumario: | State estimation of distribution systems typically relies on measurement sets with very low redundancy levels. In this paper, this fact is exploited by first solving a conventional load flow, using exclusively a critical set of measurements, and then compensating the solution to account for the few redundant measurements available. This leads to a suboptimal but sufficiently accurate estimate. It is shown how the sparse triangular factorization of the load flow Jacobian matrix can be fully exploited throughout the compensation-based procedure, preventing in this way the ill-conditioning associated with the gain matrix arising in the conventional least-squares formulation. Simulation results are provided for measurement configurations customarily found in distribution systems, showing the potential advantages of the proposed methodology. |
|---|