Variable structure control for three-phase LCL-filtered inverters using a reduced converter model
This paper presents a new concept in active damping techniques using a reduced model of a LCL-filtered grid connected inverter. The presence of the LCL filter complicates the design of the inverter control scheme, particularly when uncertainties in the system parameters, especially in the grid induc...
| Autores: | , , , , |
|---|---|
| Tipo de recurso: | artículo |
| Fecha de publicación: | 2017 |
| País: | España |
| Institución: | Universitat Politècnica de Catalunya (UPC) |
| Repositorio: | UPCommons. Portal del coneixement obert de la UPC |
| Idioma: | inglés |
| OAI Identifier: | oai:upcommons.upc.edu:2117/106253 |
| Acceso en línea: | https://hdl.handle.net/2117/106253 https://dx.doi.org/10.1109/TIE.2017.2716881 |
| Access Level: | acceso abierto |
| Palabra clave: | Electric filters, Active Electric inverters Kalman filtering Sliding mode control Impedance Inverters Robustness Damping Control systems Mathematical model Inductance Sliding mode control (SMC) LCL filter Kalman filter (KF) Reduced model Xarxes elèctriques -- Informàtica Kalman, Filtratge de Àrees temàtiques de la UPC::Enginyeria electrònica Àrees temàtiques de la UPC::Enginyeria elèctrica |
| Sumario: | This paper presents a new concept in active damping techniques using a reduced model of a LCL-filtered grid connected inverter. The presence of the LCL filter complicates the design of the inverter control scheme, particularly when uncertainties in the system parameters, especially in the grid inductance, are considered. The proposed control algorithm is addressed to overcome such difficulties using a reduced model of the inverter in a state observer. In this proposal, two of the three state variables of the system are obviated from the physical inverter model and only the inverter side current is considered. Therefore, the inverter side current can be estimated emulating the case of an inverter with only one inductor, thus eliminating the resonance problem produced by the LCL filter. Besides, in the case of a distorted grid, the method allows to estimate the voltages at the point of common coupling free of noise and distortion without using any PLL-based synchronization. To complete the control scheme, a theoretical stability analysis is developed considering the effect of the observer, the system discretization and the system parameters deviation. Experimental and comparative evaluation results are presented to validate the effectiveness of the proposed control scheme |
|---|