Modeling and design of the vector control for a three-phase single-stage grid-connected PV system with LVRT capability according to the spanish grid code
This article deals with the vector control in dq axes of a three-phase grid-connected photovoltaic system with single-stage topology and low-voltage-ride-through capability. The photovoltaic generator is built using an array of several series-parallel Suntech PV modules and is modeled as a Lookup Ta...
| Autores: | , , , |
|---|---|
| Tipo de recurso: | artículo |
| Estado: | Versión publicada |
| Fecha de publicación: | 2019 |
| País: | España |
| Institución: | Universidad Politécnica de Cartagena(UPCT) |
| Repositorio: | Repositorio Digital UPCT |
| OAI Identifier: | oai:repositorio.upct.es:10317/9461 |
| Acceso en línea: | http://hdl.handle.net/10317/9461 |
| Access Level: | acceso abierto |
| Palabra clave: | Vector control Low-voltage-ride-through Grid-connected photovoltaic system Voltage sags Active and reactive powers Arquitectura y Tecnología de Computadoras 2106.01 Energía Solar 2212.03 Energía (Física) |
| Sumario: | This article deals with the vector control in dq axes of a three-phase grid-connected photovoltaic system with single-stage topology and low-voltage-ride-through capability. The photovoltaic generator is built using an array of several series-parallel Suntech PV modules and is modeled as a Lookup Table (two-dimensional; 2-D). The requirements adopted when grid voltage sags occur are based in both the IEC 61400-21 European normative and the allowed amount of reactive power to be delivered according to the Spanish grid code, which avoids the disconnection of the inverter under grid faults by a limitation in the magnitude of the three-phase output inverter currents. For this, the calculation of the positive- and negative-sequences of the grid voltages is made and a conventional three-phase Phase-Locked Loop is used for the inverter-grid synchronization, allowing the control of the active and reactive powers solely with the dq components of the inverter currents. A detailed enhanced flowchart of the control algorithm with low-voltage-ride-through capability is presented and several simulations and experiments using Matlab/SIMULINK and the Controller Hardware-in-the-Loop simulation technique, respectively, are run for several types of one- and three-phase voltage sags in order to validate its behavior. |
|---|