Design and experimental evaluation tests of a Takagi–Sugeno power system stabiliser

In this study, the design, implementation and experimental evaluation tests of a Takagi–Sugeno power system stabiliser (TSPSS) controller is presented. The controller was designed in order to provide a good damping for dominant electromechanical oscillations in power systems for the set of allowed o...

Descripción completa

Detalles Bibliográficos
Autores: Nogueira, Fabrício Gonzalez, Barra Júnior, Walter, Costa Júnior, Carlos Tavares da, Moraes, Anderson Roberto Barbosa de, Gomes, Marcus Ciro Martins, Lana, Jânio José de
Tipo de recurso: artículo
Estado:Versión publicada
Fecha de publicación:2014
País:Brasil
Institución:Universidade Federal do Ceará (UFC)
Repositorio:Repositório Institucional da Universidade Federal do Ceará (UFC)
Idioma:inglés
OAI Identifier:oai:repositorio.ufc.br:riufc/69513
Acceso en línea:http://www.repositorio.ufc.br/handle/riufc/69513
Access Level:acceso abierto
Palabra clave:Takagi–Sugeno power system stabiliser (TSPSS)
Electromechanical oscillations
Laboratory scale power system
Descripción
Sumario:In this study, the design, implementation and experimental evaluation tests of a Takagi–Sugeno power system stabiliser (TSPSS) controller is presented. The controller was designed in order to provide a good damping for dominant electromechanical oscillations in power systems for the set of allowed operating conditions. In the proposed TSPSS controller, such requirement was accomplished by implementing a supervision scheme which performs the adaptation of the TSPSS parameters at each sample time, according to the current detected plant operating condition. The TSPSS controller has been implemented as a microcontroller-based embedded system and its performance was assessed by performing experimental tests in a laboratory scale (10 kVA) power system as well as in field tests performed in a large (350 MVA) generating unit, at Tucuruí Hydroelectric Power Plant. The experimental results also show the good performance of the TSPSS to cope with varying plant operation condition.