Single-phase and two-phase secondary coolants: simulation and evaluation of their thermophysical properties
This paper makes a comparative analysis of the thermophysical properties of ice slurry with conventional single-phase secondary fluids used in thermal storage cooling systems. The ice slurry is a two-phase fluid consisting of water, antifreeze and ice crystals. It is a new technology that has shown...
| Autores: | , , |
|---|---|
| Tipo de recurso: | artículo |
| Estado: | Versión publicada |
| Fecha de publicación: | 2011 |
| País: | Brasil |
| Institución: | Universidade Federal do Rio Grande do Norte (UFRN) |
| Repositorio: | Repositório Institucional da UFRN |
| Idioma: | inglés |
| OAI Identifier: | oai:repositorio.ufrn.br:123456789/45343 |
| Acceso en línea: | https://repositorio.ufrn.br/handle/123456789/45343 |
| Access Level: | acceso abierto |
| Palabra clave: | Ice Slurry Secondary Fluids Thermophysical Properties Thermal Storage Cooling |
| Sumario: | This paper makes a comparative analysis of the thermophysical properties of ice slurry with conventional single-phase secondary fluids used in thermal storage cooling systems. The ice slurry is a two-phase fluid consisting of water, antifreeze and ice crystals. It is a new technology that has shown great energy potential. In addition to transporting energy as a heat transfer fluid, it has thermal storage properties due to the presence of ice, storing coolness by latent heat of fusion. The single-phase fluids analyzed are water-NaCl and water-propylene glycol solutions, which also operate as carrier fluids in ice slurry. The presence of ice changes the thermophysical properties of aqueous solutions and a number of these properties were determined: density, thermal conductivity and dynamic viscosity. Data were obtained by software simulation. The results show that the presence of 10% by weight of ice provides a significant increase in thermal conductivity and dynamic viscosity, without causing changes in density. The rheological behavior of ice slurries, associated with its high viscosity, requires higher pumping power; however, this was not significant because higher thermal onductivity allows a lower mass flow rate without the use of larger pumps. Thus, the ice slurry ensures its high potential as a secondary fluid in thermal storage cooling systems, proving to be more efficient than single-phase secondary fluids |
|---|