Online detection of interturn short-circuit fault in induction motor based on 5th harmonic current tracking using Vold-Kalman filter

In this paper we propose a strategy for real-time detection of interturn shortcircuit faults (ISCF) on three-phase induction motor (IM) by using a VoldKalman filter (VKF) algorithm. ISCF produce a thermal stress into the stator winding due to large current that flows through the short-circuited turn...

ver descrição completa

Detalhes bibliográficos
Autores: Mazzoletti, Manuel Armando, Gentile, Francisco R., Donolo, Pablo Daniel, Bossio, Guillermo Rubén
Formato: artículo
Estado:Versión publicada
Fecha de publicación:2023
País:Argentina
Recursos:Consejo Nacional de Investigaciones Científicas y Técnicas
Repositorio:CONICET Digital (CONICET)
Idioma:inglés
OAI Identifier:oai:ri.conicet.gov.ar:11336/229929
Acesso em linha:http://hdl.handle.net/11336/229929
Access Level:acceso abierto
Palavra-chave:FAULT DETECTION
INDUCTION MOTOR
INTERTURN SHORT-CIRCUIT
VOLD-KALMAN FILTER
https://purl.org/becyt/ford/2.2
https://purl.org/becyt/ford/2
Descrição
Resumo:In this paper we propose a strategy for real-time detection of interturn shortcircuit faults (ISCF) on three-phase induction motor (IM) by using a VoldKalman filter (VKF) algorithm. ISCF produce a thermal stress into the stator winding due to large current that flows through the short-circuited turns.Therefore, incipient fault detection is required in order to avoid catastrophic failures such as phase to phase, or phase to ground faults. The strategy is based on an analytical IM model that includes a ISCF fault in any of the phase windings and considering the h-th harmonic in the voltage supply. Based on equivalent electrical circuits with harmonics in sequence components, wepropose a strategy for detection of an ISCF on IM by tracking the 5th harmoniccurrent component using a VKF algorithm. The proposed model is experimentally validated using a three-phase IM with modified stator windings to generate ISCF. Also, the IM is feeded by a programmable voltage source to synthesize distorted voltage supply with the 5th harmonic. Theresults demonstrated that the positive-sequence magnitude for the 5th harmonic current component is a good indicator of the fault severity once it exceeds a threshold limit value, even under load variations and unbalanced voltages.